Information based on query as of Wednesday, June 26, 2024.
Permit Information
Permit NumberMEC20-00300
StatusFinaled
Name HOME HEATING & A/C INC
Site Address 2516 S APPLE ST
Project NameVirtus Services LLC - T.I.
Customer Number 
ePlanReviewNo
Description
Alteration: Build Ductwork and gas line
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/31/20204/1/20204/1/2020APASS
DetailsJack Reynolds
Final inspection as the inspection from Jim Page passed Phone #: ###-#### Inspection requested via web by Devry King
- final ok occ card signed
Final3/31/20203/31/20203/31/2020PCANC
DetailsJack Reynolds
@ 12:30 Fire , life & safety inspector will be there. Installer will be there customer is wanting this to be finaled off either at the same time or soon there after Phone #: ###-#### >> Inspection requested via web by Devry King Inspection cancelled from web by: Devry King
Final3/17/20203/17/20203/17/2020PPEND
DetailsJack Reynolds
Per inspector on 3/13/20 This needs tested for operation of smoke shut down. This was inspectors request from our final inspection request. Phone #: ###-#### Inspection requested via web by Devry King
- fire inspector will need to inspect smoke shut down of RTU. I have been in contact with Joe hvac contractor and owner of building about this topic.
Final3/12/20203/12/20203/12/2020PFAIL
DetailsJack Reynolds
Jonathon is the contact. Installer is requesting a pressure, rough in and final inspection Phone #: ###-#### Inspection requested via web by Devry King
- large unit on south side of building needs to be checked for a smoke detector. And will need to be tested for operation of smoke shut down.
Rough-in3/12/20203/12/20203/12/2020PPASS
DetailsJack Reynolds
Jonathon is the contact. Installer is requesting a pressure, rough in and final inspection Phone #: ###-#### Inspection requested via web by Devry King
-R/I ok
Pressure Test3/12/20203/12/20203/12/2020PPASS
DetailsJack Reynolds
Jonathon is the contact. Installer is requesting a pressure, rough in and final inspection Phone #: ###-#### Inspection requested via web by Devry King
- 20lb gas pressure test ok
Rough-in2/19/20202/19/20202/19/2020PFAIL
DetailsJack Reynolds
This is a duct work inspection only. Joe our installer will be there from 8:15 am -2 pm Phone #: ###-#### Inspection requested via web by Devry King
- changes to HVAC need to be submitted to city for review
- will need to see gas pressure test on new gas line
- water heater flue needs 1" clearances and insulation shield installed
- exhaust fans in showers need installed