Final | 2/27/2020 | 2/27/2020 | 2/27/2020 | P | PASS |
Jack Reynolds
|
|
|
Plumbing permit pulled Phone #: ###-#### Inspection requested via web by Justin Osterhout - final ok
|
Final | 2/19/2020 | 2/25/2020 | 2/25/2020 | A | PART |
Jack Reynolds
|
|
|
Call Tech on site - Bill ###-#### in route to inspection Phone #: ###-#### Inspection requested via web by Justin Osterhout - all corrections are ok - homeowner is going to pull plumbing permit for vent. Once plumbing permit is pulled mechanical permit can be finaled
|
Final | 2/14/2020 | 2/19/2020 | 2/19/2020 | A | FAIL |
Jack Reynolds
|
|
|
Call Chris in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout - A/C need locking caps - line set penetration into cover needs sealed - b vent needs 1" clearances - condensate line needs supported - will need install crew onsite to gain access to attic to furnace - talked with homeowner about getting a plumbing permit for plumbing vent that terminates in attic
|