Rough-in | 3/6/2020 | 3/10/2020 | 3/10/2020 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Denise Colin - R/I ok
|
Rough-in | 3/3/2020 | 3/4/2020 | 3/4/2020 | A | FAIL |
Jack Reynolds
|
|
|
Mike Phone #: ###-#### - bathroom exhaust ok - line set rips ok - floor boots ok - need to see 6" fresh air installed and return in attic insulated - need updated Man J onsite - need to see exhaust fans,duct work added to permit and transfer airs into bedrooms by final
|
Rough-in | 2/14/2020 | 2/18/2020 | 2/18/2020 | A | FAIL |
Jack Reynolds
|
|
|
Please call Mike when on the way. Thank you!! Phone #: ###-#### Inspection requested via web by Denise Colin - Man J needs updated for furnace and approved by City - bathroom exhausts need finished - line set arma flex in crawl needs repaired - all bedrooms will need transfer air or ducted returns by final - all floor boots need sealed - need to add duct work and exhaust fans to permit
|
Final | 8/13/2020 | 8/14/2020 | | P | |
Jack Reynolds
|
|
|
Please call when on the way Phone #: ###-#### >> Inspection requested via web by Denise Colin
|