Permit Information
Permit NumberMEC20-00685
StatusIssued
Name YMC INC
Site Address 3710 W KOOTENAI ST
Project Name 
Customer Number3716801
ePlanReviewNo
Description
Alteration or Repair: Replacing flue for furnace and water heater and kitchen range hood venting// 2/25/20 duct work TCH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Rough-in2/25/20202/26/20202/26/2020APASS
DetailsJack Reynolds
For Make up air for range hood, please call contractor 30 minutes in advance for access at ###-#### and call Ryan with questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- make up air and range vent ok R/I ok
Rough-in2/19/20202/19/20202/19/2020PPASS
DetailsJack Reynolds
Please call contractor 30 minutes in advance for access at ###-#### and call Ryan with questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum
-R/I ok
Rough-in2/18/20202/18/20202/18/2020PFAIL
DetailsJack Reynolds
Please call contractor 30 minutes in advance for access at ###-#### and call Ryan with questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- all b vent needs 1" clearances
- need to see insulation sheild in attic
- furnace connection to common vent needs to connect at bottom of b vent wye and water heater needs to connect at the highest point in the b vent wye
- range hood is a 600 cfm and will need make up air or be under 400 cfm