Final | 5/8/2020 | 5/8/2020 | 5/8/2020 | P | PASS |
Brian Scoles
|
|
|
Corrections made please reinspect garage code 3484 Phone #: ###-#### Inspection requested via web by Oleg Chervak- final
|
Final | 5/6/2020 | 5/6/2020 | 5/6/2020 | P | FAIL |
Brian Scoles
|
|
|
corrections made please re-inspect, thank you, garage code 3484 Phone #: ###-#### Inspection requested via web by Oleg Chervak- lineset penetration needs sealed weather tight- reinspection fee issued
|
Final | 5/5/2020 | 5/5/2020 | 5/6/2020 | P | FAIL |
Brian Scoles
|
|
|
CORRECTIONS MADE PLEASE RE-INSPECT 3484 Phone #: ###-#### Inspection requested via web by Oleg Chervak- need locking caps on a/c service ports- siding needs replaced around lineset and sealed-
|
Final | 5/4/2020 | 5/4/2020 | 5/4/2020 | P | FAIL |
Brian Scoles
|
|
|
GC 3484 Phone #: ###-#### Inspection requested via web by Oleg Chervak- need condenser set and lineset tied in at coil and repair kinked lineset at condenser location and tied in- need to remove white paint on b vent in garage at ceiling
|
Rough-in | 2/25/2020 | 2/26/2020 | 2/26/2020 | A | PASS |
Brian Scoles
|
|
|
manj will be on site at furnace location information bin. Phone #: ###-#### Inspection requested via web by Oleg -R/I ok
|
Rough-in | 2/25/2020 | 2/25/2020 | 2/25/2020 | P | FAIL |
Brian Scoles
|
|
|
Ready for inspection Phone #: ###-#### Inspection requested via web by Oleg Chervak- need city approved man j onsite for inspection none found
|
Pressure Test | 2/25/2020 | 2/25/2020 | 2/25/2020 | P | PASS |
Brian Scoles
|
|
|
Bad gauge, please reinspect Phone #: ###-#### Inspection requested via web by Oleg Chervak- 5lb flue pass
|
Rough-in | 2/21/2020 | 2/24/2020 | 2/24/2020 | P | NR |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- still installing
|
Pressure Test | 2/21/2020 | 2/24/2020 | 2/24/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location- flue test under 5 psi not holding
|
Rough-in | 2/21/2020 | 2/21/2020 | 2/21/2020 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
|