Final | 4/23/2020 | 4/23/2020 | 4/23/2020 | A | PASS |
Jack Reynolds
|
|
|
- final ok
|
Final | 4/22/2020 | 4/23/2020 | 4/23/2020 | A | NH |
Jack Reynolds
|
|
|
Please Call Phone #: ###-#### Inspection requested via web by Sean Hyten - No access - called owner and left voicemail - left notice on front door
|
Final | 4/14/2020 | 4/15/2020 | 4/15/2020 | A | PART |
Jack Reynolds
|
|
|
Please Call. Phone #: ###-#### Inspection requested via web by Sean Hyten - extended rigid gas line to range needs supported to wall - appliance flex connector needs replaced with new
|
Final | 4/9/2020 | 4/10/2020 | 4/10/2020 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Sean Hyten - no access
|
Rough-in | 2/18/2020 | 2/19/2020 | 2/19/2020 | A | FAIL |
Jack Reynolds
|
|
|
Call for lock box code Phone #: ###-#### Inspection requested via web by Sean Hyten - all CSST in crawl needs supported per spec - need BTU information on range - only one appliance flex connector can be used on range gas line - gas piping connection to meter on north side looks to be under a car port and will need a crash bar/ protection post installed - 1/2 CSST gas pressure test fail gauge would not zero out - 5lb flue pressure test for water heater ok - 20lb gas pressure test to water heater ok
|