Information based on query as of Thursday, June 27, 2024.
Permit Information
Permit NumberMEC20-00839
StatusFinaled
Name 45TH PARALLEL HVAC LLC
Site Address 7800 W USTICK RD Unit: 100
Project NameDr. Paige Schmidt TI
Customer Number33033
ePlanReviewNo
Description
Alteration: Redirect return airs, floor registers
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/28/20204/28/20204/28/2020PPASS
DetailsBrian Scoles
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson- final ok- no card onsite
Card not on site to sign4/28/20204/28/20204/28/2020PPASS
DetailsBrian Scoles
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson- no card onsite
Final4/27/20204/28/20204/28/2020ACANC
DetailsBrian Scoles
Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
Final4/24/20204/24/20204/24/2020PPART
DetailsBrian Scoles
Final and grid inspection Phone #: ###-#### Inspection requested via web by David Nelson- need city approved pritns onsite only 2 pages could be found- need to secure 6" galv piping in couple more places and finishing sealing joints- need to fire caulk both penetrations at roof per prints- need to seal exhaust fan at ceiling 2 holes in it- any hanger screwed into wall needs firecaulked on screw head per discussion with bld inspector-need to verify return register installed are approved- recall in final when ready
Rough-in3/13/20203/16/20203/16/2020ADONE
DetailsBrian Scoles
Meeting on site with builder/contractor 10:00am Phone #: ###-#### Inspection requested via web by David Nelson- meet to discuss med gas room on shaft and ducting will require plan mod and engineers approved drawings
Rough-in3/16/20203/16/20203/16/2020APART
DetailsBrian Scoles
Meeting on site with builder/contractor 10:00am Phone #: ###-#### Inspection requested via web by David Nelson- ok to cover excluding med gas room- will need plan mod approved for routing of ducting
Rough-in3/13/20203/13/20203/13/2020PFAIL
DetailsBrian Scoles
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson- duct work can not run in wall for outside air- need ran per print with in 12 inches AFF in rated shaft- any ducting, wires need rerouted outside of shaft nothing can penetrate shatf or pass thru- met with bld inspector he left notice front door for GC to call him for a conference
Rough-in3/9/20203/10/20203/10/2020PCANC
DetailsBrian Scoles
access lock box on gas meter 1027 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
Rough-in3/5/20203/6/20203/6/2020AFAIL
DetailsBrian Scoles
Access lock box on gas meter 1027 Phone #: ###-#### Inspection requested via web by David Nelson
1- exhaust fan and outside air needs ran per approved drawings see key note 4 and 9 on ME-2 for details/ need to coordinate with GC on 1 hour shaft thats required for med gas room per A2.1 symbol 5 and have a conference with building inspector on this onsite

left notice on door
Rough-in2/28/20203/2/20202/28/2020PCANC
DetailsBrian Scoles
access lockbox on gas meter 1027 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
Rough-in2/27/20202/28/20202/28/2020AFAIL
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by David Nelson
- exhaust duct not installed per approved plans key notes 4,5,
- 4x4 fresh air not installed key note 9
- dryer duct needs to teminate out the roof not in the attic, also needs nail plate at top plate