Final | 4/28/2020 | 4/28/2020 | 4/28/2020 | P | PASS |
Brian Scoles
|
|
|
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson- final ok- no card onsite
|
Card not on site to sign | 4/28/2020 | 4/28/2020 | 4/28/2020 | P | PASS |
Brian Scoles
|
|
|
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson- no card onsite
|
Final | 4/27/2020 | 4/28/2020 | 4/28/2020 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Final | 4/24/2020 | 4/24/2020 | 4/24/2020 | P | PART |
Brian Scoles
|
|
|
Final and grid inspection Phone #: ###-#### Inspection requested via web by David Nelson- need city approved pritns onsite only 2 pages could be found- need to secure 6" galv piping in couple more places and finishing sealing joints- need to fire caulk both penetrations at roof per prints- need to seal exhaust fan at ceiling 2 holes in it- any hanger screwed into wall needs firecaulked on screw head per discussion with bld inspector-need to verify return register installed are approved- recall in final when ready
|
Rough-in | 3/13/2020 | 3/16/2020 | 3/16/2020 | A | DONE |
Brian Scoles
|
|
|
Meeting on site with builder/contractor 10:00am Phone #: ###-#### Inspection requested via web by David Nelson- meet to discuss med gas room on shaft and ducting will require plan mod and engineers approved drawings
|
Rough-in | 3/16/2020 | 3/16/2020 | 3/16/2020 | A | PART |
Brian Scoles
|
|
|
Meeting on site with builder/contractor 10:00am Phone #: ###-#### Inspection requested via web by David Nelson- ok to cover excluding med gas room- will need plan mod approved for routing of ducting
|
Rough-in | 3/13/2020 | 3/13/2020 | 3/13/2020 | P | FAIL |
Brian Scoles
|
|
|
access 1027 Phone #: ###-#### Inspection requested via web by David Nelson- duct work can not run in wall for outside air- need ran per print with in 12 inches AFF in rated shaft- any ducting, wires need rerouted outside of shaft nothing can penetrate shatf or pass thru- met with bld inspector he left notice front door for GC to call him for a conference
|
Rough-in | 3/9/2020 | 3/10/2020 | 3/10/2020 | P | CANC |
Brian Scoles
|
|
|
access lock box on gas meter 1027 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Rough-in | 3/5/2020 | 3/6/2020 | 3/6/2020 | A | FAIL |
Brian Scoles
|
|
|
Access lock box on gas meter 1027 Phone #: ###-#### Inspection requested via web by David Nelson 1- exhaust fan and outside air needs ran per approved drawings see key note 4 and 9 on ME-2 for details/ need to coordinate with GC on 1 hour shaft thats required for med gas room per A2.1 symbol 5 and have a conference with building inspector on this onsite
left notice on door
|
Rough-in | 2/28/2020 | 3/2/2020 | 2/28/2020 | P | CANC |
Brian Scoles
|
|
|
access lockbox on gas meter 1027 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Rough-in | 2/27/2020 | 2/28/2020 | 2/28/2020 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson - exhaust duct not installed per approved plans key notes 4,5, - 4x4 fresh air not installed key note 9 - dryer duct needs to teminate out the roof not in the attic, also needs nail plate at top plate
|