Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC20-00861
StatusFinaled
Name JOSE LAGUNAS
Site Address 2136 S LONGMONT AVE
Project Name 
Customer Number013
ePlanReviewNo
Description
Complete HVAC Installation: New hvac system and ducting
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/7/20205/7/20205/7/2020PPASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Jose Lagunas
- final ok
Rough-in3/3/20203/3/20203/3/2020PPASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Jose Lagunas
-R/I ok
Rough-in3/2/20203/2/20203/2/2020PFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Jose Lagunas
- b vent upstairs needs 1" clearances
- combustion air openings are not big enough, size openings per btu ratings of equipment being installed in mech room
Pressure Test3/2/20203/2/20203/2/2020PPASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Jose Lagunas
- 5lb flue pressure test ok
- 20lb gas pressure test ok
- tagged meter location