Final | 6/8/2020 | 6/9/2020 | 6/9/2020 | A | PASS |
Chad Schwendiman
|
|
|
CORRECTIONS MADE PLEASE REINSPECT Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Final | 6/5/2020 | 6/5/2020 | 6/5/2020 | P | FAIL |
Brian Scoles
|
|
|
garage doors will be open Phone #: ###-#### Inspection requested via web by Oleg Chervak- 7200 needs condenser pad leveled- 7226 need pvc intake supported and leveled horizontally- verify gas valves are on on fireplaces
|
Final | 6/1/2020 | 6/2/2020 | 6/2/2020 | A | CANC |
Brian Scoles
|
|
|
DOORS WILL BE OPEN Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
|
Pressure Test | 3/11/2020 | 3/12/2020 | 3/12/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass both units tagged meter locations- 5lb flue pass both units
|
Rough-in | 3/11/2020 | 3/12/2020 | 3/12/2020 | P | PASS |
Brian Scoles
|
|
|
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I HVAC and fireplace ok both units
|
Rough-in | 3/10/2020 | 3/11/2020 | 3/11/2020 | P | FAIL |
Brian Scoles
|
|
|
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak- 7200 1- need to resubmit man j carrier equipment installed shows payne on man j 2- gas test at zero 3- need insulation shield installed on fireplace flue 1st floor in joist bay and secure flue in chase above fireplace 4- need to seal transfer boots 5- remove metal thimble second floor attic and replace with flat metal and insulation shield needs 1" clearance to flue
7226 1- need to resubmit man j carrier equipment installed show payne on man j 2- fireplace needs secured to structure and flue needs secure to structure aboce fireplace in chase 3- need to seal transfer boots 1st floor 4- remove metal thimble piece in attic and replace with flat metal and insulation shield needs 1" clearance to flue 5 flue test at zero
left notices front room window both units
|
Pressure Test | 3/10/2020 | 3/11/2020 | 3/11/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 7200 gas test fail at 3psi- flue test pass- 7226 20lb gas pass tagged meter location- flue test at zero
|