Rough-in | 3/11/2020 | 3/12/2020 | 3/12/2020 | A | PASS |
Ben Livingston
|
|
|
Inspection requested via web by Loren Bailey
|
Rough-in | 3/10/2020 | 3/11/2020 | 3/11/2020 | P | FAIL |
Ben Livingston
|
|
|
Inspection requested via web by Loren Bailey - cannot have screws in dryer vent
|
Rough-in | 3/10/2020 | 3/10/2020 | 3/10/2020 | P | FAIL |
Ben Livingston
|
|
|
Inspection requested via web by Loren Bailey - dryer duct with premade taps are not to code, use pipe and elbows only -
|
Rough-in | 3/5/2020 | 3/6/2020 | 3/6/2020 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Loren Bailey - corrections not made
|
Rough-in | 3/3/2020 | 3/4/2020 | 3/4/2020 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Loren Bailey - duct seal in basement needs finished - line set arma flex in wall nee repaired - dryer duct needs installed at R/I and added to permit - kitchen supply boot needs ducted out of cabinet
|