Permit Information
Permit NumberMEC20-00984
StatusFinaled
Name ALLEY HEATING & COOLING
Site Address 7252 W DENTON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: duplex
complete hvac-r instillation
furnace, gas-piping, fire-place, duct-work, bath vents, dryer vent, kitchen vent, water heater vent, a/c.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/8/20206/9/20206/9/2020APASS
DetailsChad Schwendiman
CORRECTIONS MADE PLEASE REINSPECT Phone #: ###-#### Inspection requested via web by Oleg Chervak
Final6/5/20206/5/20206/5/2020PFAIL
DetailsBrian Scoles
garage doors will be open Phone #: ###-#### Inspection requested via web by Oleg Chervak- 7238 need gas piping completed to furnace- verify gas valves to fireplaces are turned on- 7252 ok
Final6/1/20206/2/20206/2/2020ACANC
DetailsBrian Scoles
DOORS WILL BE OPEN Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
Rough-in3/11/20203/12/20203/12/2020PPASS
DetailsBrian Scoles
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I HVAC and fireplace ok both units
Pressure Test3/11/20203/12/20203/12/2020PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass both units tagged meter locations- 5lb flue pass both units
Rough-in3/10/20203/11/20203/11/2020PFAIL
DetailsBrian Scoles
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak-

7238
1- need to resubmit man j carrier equipment(furnace/ac) installed and shows payne on man j
2- need to secure fireplace flue to structure 1st floor chase above fireplace
3- firecaulk missing 2nd floor at floor on fireplace flue
4- insulation shield needs 1" clearance and flue needs 1" clearance to wood in attic/ remove metal in attic around fireplace flue and replace with flat metal in place has piece from thimble and firecaulk all the way around pipe
5- missing seal on supply duct 2nd floor on both seams in chase
6- exposed insulation in crawl needs vapor barrier/taped at crawl entrance
7- need to seal transfer boots 1st floor
left notice front window

7252
1- need to resubmit man j carrier equipment (furnace/ac) installed and man j shows payne
2- need to secure fireplace flue to structure 1st floor chase above fireplace
3- need to seal transfer boots 1st floor
4- draft stop 2nd floor on fireplace flue has gap need to be flush with floor not up on one side of 2x4 and seal open hole in attic draft stop 5- need intakeon furnace needs ran to attic or outside since in house
left notice front window
Pressure Test3/10/20203/11/20203/11/2020PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass both units tagged meter location- 5lb flue pass both inits