Final | 5/11/2020 | 5/11/2020 | 5/11/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- final ok
|
Final | 5/7/2020 | 5/7/2020 | 5/7/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- no air balance report onsite
|
Rough-in | 3/26/2020 | 3/26/2020 | 3/26/2020 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- R/I ok
|
Rough-in | 3/25/2020 | 3/25/2020 | 3/25/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE 1- needs transfers installed all bedrooms 2- oval duct in laundry room wall needs extended up higher into attic 3- bedroom 3 needs supply wye branch insulated and tap needs sealed and insulated 4- remove spray foam around b vent 2nd floor at attic 5- need to insulate supply wye branch above mater bath bare metal showing
left notice front window
|
Pressure Test | 3/25/2020 | 3/25/2020 | 3/25/2020 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- 20lb gas pass tagged meter location
|