Information based on query as of Tuesday, May 7, 2024.
Permit Information
Permit NumberMEC20-01278
StatusFinaled
Name LEGENDS MECHANICAL LLC
Site Address 9619 W MACAW ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: complete hvac install
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/11/20206/12/20206/12/2020APASS
DetailsBrian Scoles
AC: 6132 Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
Rough-in4/8/20204/9/20204/9/2020APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
Rough-in4/8/20204/9/20204/8/2020PCANC
DetailsBrian Scoles
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
Rough-in4/8/20204/8/20204/8/2020PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- need to reroute dryer duct and termination box- ex fan above master shower needs plastic housing secured to fan has gap
Rough-in4/7/20204/8/20204/8/2020ANR
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- Crawl ducting needs supported 4 inches off ground on supply main
Rough-in4/7/20204/7/20204/7/2020PNR
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves
1- still installing crawl
2- exhaust flex needs hooked to fan
3- dryer duct needs rerouted outside of wall and not behind dryer
4- insulation shield on water heater b vent needs to go all the way to roof pitch
Pressure Test4/7/20204/7/20204/7/2020PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass tagged meter location- 5lb flue pass