Final | 4/2/2020 | 4/2/2020 | 4/2/2020 | P | PASS |
Brian Scoles
|
|
|
Replaced 40 amp breakers in panel and disconnect with 30 amp breakers. Could not get 6" clearance to condensate drain line without messing the condensate drain line all up. Complete flue is now double wall flue. 1" clearance to condensate drain line and armaflex. Thank you. Phone #: ###-#### Inspection requested via web by jeremy wanders- final ok pics sent via text
|
Final | 3/31/2020 | 3/31/2020 | 3/31/2020 | P | FAIL |
Brian Scoles
|
|
|
Replace existing 80% furnace and ac with a new 80% furnace and ac with same specs as the old one. Home already had carbon monoxide sensors installed. Home owner is working from home and should be there. Call me if you need any thing. Thank you. Jeremy Phone #: ###-#### Inspection requested via web by jeremy wanders 1- breaker in garage and disconnect outside is 40 amp needs 30 amp max per condenser 2- single wall flue needs 6" clearance to arma flex and pvc primary drain
|