Mec-Request for Extension | 8/3/2020 | 8/4/2020 | 8/4/2020 | A | PASS |
Brian Scoles
|
|
|
We are close to finishing the project, can you do a parcel inspection so we dont loose the building permit, it''s going to expire soon. Phone #: ###-#### Inspection requested via web by Oleg Chervak- permit extended til 11-4-20-
|
Conference | 4/8/2020 | 4/8/2020 | 4/8/2020 | P | DONE |
Brian Scoles
|
|
|
PLEASE MEET ME ON THE JOB WITH BUILDER, CALL ME TO SCHEDULE Phone #: ###-#### Inspection requested via web by Oleg Chervak- per conversation with engineer by phone mechanical contractor will submit drawing to him and he will send to city for review- need to possibly address MAU and exhaust fans for class 1 hood location is on a pitched roof- need class 1 hood instructions onsite
|
Conference | 4/6/2020 | 4/7/2020 | 4/7/2020 | P | DONE |
Brian Scoles
|
|
|
SORRY ABOUT THE WRONG ADDRESS HUMAN ERR, PLEASE CALL ANDREY FOR CONSULT, WE REALLY NEED YOU Phone #: ###-#### Inspection requested via web by Oleg Chervak- 1- need to submit mechanical and structual drawings to city for review up sizing RTY from 5 or 6 ton to 10 ton unit and will be indifferent location than approved drawings- all duct will be changed also- 2- let mechanical contractor know that workers from Utah doing grease duct will need to licensed in state of idaho prior to commencing work- went over all this onsite with Andrey-should call in for conference with building and mechanical inspectors for consultation
|
Conference | 4/6/2020 | 4/6/2020 | 4/6/2020 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wrong address- need to attach mech permit to right bld and address- reschedule conference
|