Rough-in | 5/5/2020 | 5/6/2020 | 5/6/2020 | A | PASS |
Jack Reynolds
|
|
|
screened // Tim Phone #: ###-#### - R/I ok
|
Rough-in | 4/20/2020 | 4/21/2020 | 4/21/2020 | A | FAIL |
Jack Reynolds
|
|
|
off dorin st- back garage-Tim **cleared** Phone #: ###-#### - line set penetration needs sealed and and line set needs supported - condensate line outside needs finished - exhaust fan needs to be Energy Star rated - exhaust fan duct needs sealed - make up air/ transfer grille needs installed in bathroom by final
|