Rough-in | 4/27/2020 | 4/28/2020 | 4/28/2020 | A | PASS |
Brian Scoles
|
|
|
Ready for reinspection. Man j changed Phone #: ###-#### Inspection requested via web by Russ Curtis- R/I ok- one tap in crawl needs insulated by final in master bedroom crawl opening
|
Rough-in | 4/22/2020 | 4/23/2020 | 4/23/2020 | A | FAIL |
Brian Scoles
|
|
|
Ready for rough in inspection and gas line pressure and pvc flu pressure test. House open Phone #: ###-#### Inspection requested via web by Russ Curtis 1- dryer vent can not run in 2x4 wall needs firred out or reroute in crawl 2- need 10 mil tape on gas line penetration thru wall at meter location 3- line set needs installed on R/I 4- front bedroom missing 1 supply per approved man J onsite
left correction notice at furnace
|
Pressure Test | 4/23/2020 | 4/23/2020 | 4/23/2020 | A | PASS |
Brian Scoles
|
|
|
Ready for rough in inspection and gas line pressure and pvc flu pressure test. House open Phone #: ###-#### Inspection requested via web by Russ Curtis- 20lb gas pass tagged meter location- 5lb flue x 2 ok
|