Final | 5/19/2020 | 5/19/2020 | 5/19/2020 | P | PASS |
Brian Scoles
|
|
|
final ok- corrections made
|
Final | 5/13/2020 | 5/14/2020 | 5/14/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Marisa Hone- furnace a/c coil co ok- need locking caps on a/c service ports- vinyl tubing not approved material for condesate drain and has kink in line at ceiling and drain needs grade- route new 3/4" pvc drain to existing primary drain off coil behind freezer in 3/4" pvc with barbed fitting near pump- send pic for reinspect
|