Final | 7/22/2020 | 7/22/2020 | 7/22/2020 | P | PASS |
Jack Reynolds
|
|
|
LOCK BOX 8068 Phone #: ###-#### Inspection requested via web by Aaron Alandt - final ok
|
Final | 7/21/2020 | 7/22/2020 | 7/22/2020 | A | FAIL |
Jack Reynolds
|
|
|
LOCKBOX 8068 YOU NEED TO PUSH HARD PER CONTRACTOR Phone #: ###-#### Inspection requested via web by Aaron Alandt - water heater b vent needs 1" clearances and fire caulked - gas line needs sediment trap
|
Final | 7/21/2020 | 7/21/2020 | 7/21/2020 | P | FAIL |
Brian Scoles
|
|
|
EMPTY HOUSE - LOCK BOX 8068 Phone #: ###-#### Inspection requested via web by Aaron Alandt- no access lock box does not work- need to seal lineset penetration and install locking caps on a/c service ports
|
Rough-in | 5/12/2020 | 5/12/2020 | 5/12/2020 | P | PASS |
Brian Scoles
|
|
|
call for access // Shannon Phone #: ###-####- R/I ok
|
Pressure Test | 5/12/2020 | 5/12/2020 | 5/12/2020 | P | PASS |
Brian Scoles
|
|
|
call for access // Shannon Phone #: ###-####- 20lb gas pass whole system- tagged meter location
|
Rough-in | 5/8/2020 | 5/8/2020 | 5/8/2020 | P | FAIL |
Brian Scoles
|
|
|
lock box code 8068 Phone #: ###-#### Inspection requested via web by Aaron Alandt- 1- gas test at zero 2- dryer duct needs nail plate and hole enlarged thru floor running in 3.5" wall 3- need city approved man j onsite 4- R402.4.4 rooms containing fuel burning appliances shall be installed per this code reference 5- all rips and tears on duct in crawl needs fixed and no insulation showing on main or branch lines 6- condensate line needs ran in 3/4" pvc to outside 7- w/h heater b vent needs 1" clearance at roof to combustible- range duct needs backdraft damper installed-
left notice front window
|
Rough-in | 5/8/2020 | 5/8/2020 | 5/8/2020 | P | CANC |
Brian Scoles
|
|
|
lock box code 8068 Phone #: ###-#### Inspection requested via web by Aaron Alandt
|
Pressure Test | 5/8/2020 | 5/8/2020 | 5/8/2020 | P | FAIL |
Brian Scoles
|
|
|
lock box code 8068 Phone #: ###-#### Inspection requested via web by Aaron Alandt- gauge at zero
|