Rough-in | 7/9/2020 | 7/10/2020 | 7/10/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz 1- flue test in garage failed at zero- 2- need to fix all rips and tear in arma flexboth units bare copper showing mulitple places and secure in wall in garage- 3- missing seal on range duct at exterior penetration 4- furnace in garage needs 6" OSA rsn per man j 5- fireplace needs permited and installed and gas line into appliance- no permit for this not sure whos doing 6- supply ducts to master, bedroom 3 and loft will be smashed by sheetrock and light fixtures installed under bonus room reroute individually 7- all boots need seal inside on return and supply 8- need access platforn to furnace in attic 24 inch wide and 30 inch working area in front of furnace in attic and unobstructed 9- need filter installed in return air furnace in attic or 6" OSA will need filtered 10- dryer duct needs nail plate back wall at ceiling and seal termination box to duct 11- flues need nail plates second floor and 1/4" per foot grade under bonus room in between joists has traps in it
left notice front window
|
Pressure Test | 7/9/2020 | 7/10/2020 | 7/10/2020 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- 20lb gas pass tagged meter location- 5lb flue in garage failed at zero
|