Rough-in | 7/29/2020 | 7/30/2020 | 7/30/2020 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Kristy Newkirk
|
Rough-in | 7/28/2020 | 7/29/2020 | 7/29/2020 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Kristy Newkirk - several locations still need nailplates, grey duct and dryer vent
|
Rough-in | 7/24/2020 | 7/27/2020 | 7/27/2020 | A | FAIL |
Ben Livingston
|
|
|
There is no manual j for this project.Per Troy with the city we didn''t need one. The heating and cooling load calcs are covered by the radiant floor system. I''ll email you the conversation I had with Troy. Phone #: ###-#### Inspection requested via web by Kristy Newkirk - some linesets in crawl need tobe supported - some 6" flex needs tobe connected in crawl - 1 grey flex in the wall has become disconnected - linesets, condensate piping, grey flex need nailplates in several locations
|