Rough-in | 7/20/2020 | 7/21/2020 | 7/21/2020 | A | PART |
Jack Reynolds
|
|
|
Hard lids for bathroom area Phone #: ###-#### Inspection requested via web by Beka Hereau 5- bathroom hardlids only R/I cover ok - contractor still needs to work on getting fire damper installation instructions onsite. And have city review two added firedampers in southwest corner that were not per print. - remove retaining angles on all fire dampers
|
Rough-in | 6/23/2020 | 6/24/2020 | 6/24/2020 | A | FAIL |
Jack Reynolds
|
|
|
rough in, walls and ductwork Phone #: ###-#### Inspection requested via web by Beka Hereau - partial duct seal only - will need to see all fire dampers installed and installations instructions onsite for inspection.On southwest corner of building one fire damper will need to be added since main trunkline moved south. Need mechanical engineer involved in change and the City of Boise will need to review.
|