Final | 6/17/2020 | 6/19/2020 | 6/19/2020 | P | PASS |
Brian Scoles
|
|
|
Add inspection corrections, calling for reinspect. Added pipe insulation and Freon locks, replaced breaker. Thank You Phone #: ###-#### Inspection requested via web by Dan Ricken- a/c coil co locking caps ok- corrections made
|
Final | 6/9/2020 | 6/10/2020 | 6/10/2020 | A | FAIL |
Brian Scoles
|
|
|
Final for install of new a/c and indoor coil. someone is always home, garage is unlocked as this is a family care home. Phone #: ###-#### Inspection requested via web by Dan Ricken- arma flex needs completed to coil in garage to coil enclosure- breaker installed in panel is 30 amp and max amp for condenser is 25 amps max- need locking caps on a/c service ports- recall in when corrections made
|