Rough-in | 8/4/2020 | 8/5/2020 | 8/5/2020 | A | PASS |
Brian Scoles
|
|
|
Approved manual on site, corrections made Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok- will need booster fan on dryer duct installed by final dryer duct over 35 feet- talked to Peter about this
|
Pressure Test | 8/4/2020 | 8/5/2020 | 8/5/2020 | A | PASS |
Brian Scoles
|
|
|
Approved manual on site, corrections made Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location- 5lb flue pass
|
Rough-in | 7/30/2020 | 7/30/2020 | 7/30/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak 1- need to fix all rips and tears in arma flex in attic bare copper can be seen 2- low voltage wire laying on water heater b vent needs to support 3- gas gauge wont zero out 4- need to resubmit man j for equipment installed has carrier man shows payne and have approved one onsite for next inspection 5- range duct oval thru ceiling 6- all registers in ceiling need sealed 7- need to support exhaust ducting from master bath in attic of den/office 8- supply and return ducting in chase need metal installed where penetrates wall and attic and draftstop with fire caulk- flex duct can not run thru floors, walls or ceilings per bld code 9- bath exhaust 2nd floor needs supported 10-fresh air needs to be ran in 8" not 6" per man j
left notice window by fireplace
|
Pressure Test | 7/30/2020 | 7/30/2020 | 7/30/2020 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- gauge wont zero out
|