Permit Information
Permit NumberMEC95-01873
StatusExpired
Name A-1 HEATING & AIR CONDITIONING
Site Address 2828 W AIRPORT WAY
Project Name 
Customer Number 
ePlanReview 
Description
11/20/95- CHEVRON "C" STORE WITH GAS PUMPS AND LUBE CENTER * 1" SOFT (2) GAS PACK ROOF TOP UNITS (2) SPACE ROY HEATER UNITS (1) UNIT HEATER, FIRE DAMPERS BLDG #95-0905-$33,928.00-FINAL CERTIFICATE OF VALUE ON FILE.MPM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final3/29/19963/29/19963/29/1996PPASS
DetailsDave Lightfoot
03/29/96 337 - FNL -OK FINAL SIGN PERM OCC
INSP - Final3/29/19963/29/19963/29/1996PPASS
DetailsDave Lightfoot
03/29/96 337 - FNL -OK FINAL SIGN PERM OCC
INSP - Partial final3/28/19963/28/19963/28/1996PFAIL
DetailsDave Lightfoot
03/28/96 337 - EVERYTHING ABOVE THE CEILING CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Framing/ Rough-in2/28/19962/28/19962/28/1996PPASS
DetailsDave Lightfoot
02/28/96 337 - DAVE CAROL WOULD LIKE YOU TO CALL PAT AT ###-#### BEFORE GP -OK GAS PIPING RGHN-OK ROUGH IN
INSP - Gas piping2/26/19962/26/19962/26/1996 FAIL
DetailsDave Lightfoot
/ / 337 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED GAS TEST FAIL NEED FIRE DAMPER ACCESS NEED TO LOCTITE UNION IN GAS PIPE
INSP - Gas piping2/26/19962/26/19962/26/1996 FAIL
DetailsDave Lightfoot
/ / 337 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED GAS TEST FAIL NEED FIRE DAMPER ACCESS NEED TO LOCTITE UNION IN GAS PIPE
INSP - Framing/ Rough-in2/20/19962/21/19962/21/1996APART
DetailsDave Lightfoot
02/20/96 337 - REINSPECTION PLEASE CALL PAT WHEN READY ###-#### RGHN-OK ROUGH IN PART R/I MCDONALDS CHEVRON STORE ONLY
INSP - Duct work2/15/19962/15/19962/15/1996PFAIL
DetailsDave Lightfoot
02/15/96 337 - UNIT 1 CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Gas pressure test11/22/199511/24/199511/24/1995APASS
DetailsAlan Hauser
11/22/95 350 - THANKS ALAN THIS IS FOR FRIDAY AM GAS PIPING OK TO THE CARWASH BUILDING, BOTH ENDS OF THE PIPE ARE VENTED OUTSIDE OF EACH BUILDING.
INSP - Gas pressure test11/22/199511/22/199511/22/1995PFAIL
DetailsDave Lightfoot
11/22/95 337 - REINSPECTION CORR-CORREC-CALL FOR REINSP WHEN COMPLETED SIEEVE AND VENT NOT CORRECT
INSP - Gas pressure test11/20/199511/21/199511/21/1995AFAIL
DetailsDave Lightfoot
11/20/95 337 - SEE ATTACHED SHEETS IN YOUR BOX CORR-CORREC-CALL FOR REINSP WHEN COMPLETED gas pipe is beiow slab