BLD-Final | 3/16/2004 | 3/17/2004 | 3/17/2004 | P | PASS |
Russ Owen
|
|
|
###-#### gary ok perm oc. 3/16/2004 11:21:40 PM
|
FIR-Final | 3/16/2004 | 3/17/2004 | 3/17/2004 | A | PASS |
Troy Cobbley
|
|
|
fire life safety finaled. Structural inspector please verify the three new offices door hardware is changed to approved type. 3/17/2004 9:27:04 AM
|
Permanent Occupancy | | 3/17/2004 | 3/17/2004 | | DONE |
|
|
|
|
BLD-Final | 3/11/2004 | 3/11/2004 | 3/11/2004 | P | PART |
Russ Owen
|
|
|
gary ; Phone #: ###-#### Internet Inspection Request from: Annette Moore posted c/n. 3/10/2004 9:59:44 PM
|
BLD-Final | 3/8/2004 | 3/9/2004 | 3/9/2004 | A | NR |
Russ Owen
|
|
|
Mike -- he is having his FIR final this a.m. too, for occupany. thanks.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes. No plan on site, also fire inspecdtor was here before me and could not get in ,I informed person at site, that plan needs to be on site and fire sign off prior to me. 3/8/2004 7:32:51 PM
|
FIR-Final | 3/9/2004 | 3/9/2004 | 3/9/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide "Door to remain unlocked during business hours"sticker at the main exit. Remove manual flush bolts at the main exit. Provide approved door hardware on the north exit door (remove keyed hardware). Provide fire extinguishers. One in the office area and one in the shop area with current inspection tags and mounted at 48" AFF. Remove dead bolts on all doors. 3/9/2004 2:08:04 PM
|
FIR-Final | 3/8/2004 | 3/9/2004 | 3/9/2004 | A | FAIL |
Troy Cobbley
|
|
|
called Mike to set up access into business and left message. Stopped at project building is locked 3/9/2004 8:52:35 AM
|