BLD-Final | 8/30/2004 | 8/31/2004 | 8/31/2004 | P | PASS |
Jim Storey
|
|
|
marva; Phone #: ###-#### Internet Inspection Request from: Annette Moore. Final inspection complete.
|
FIR-Final | 8/30/2004 | 8/31/2004 | 8/31/2004 | A | PASS |
Rick Jackson
|
|
|
marva; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Permanent Occupancy | | 8/31/2004 | 8/31/2004 | | DONE |
|
|
|
|
BLD-Final | 8/25/2004 | 8/26/2004 | 8/26/2004 | A | CANC |
Jim Storey
|
|
|
marva; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles trans. to bob a. 8/26/2004 8:10:37 AM
|
FIR-Final | 8/25/2004 | 8/26/2004 | 8/26/2004 | A | NR |
Rick Jackson
|
|
|
marva; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need fire alarm permit approved and tested prior to signing this MIS permit off 8/26/2004 10:25:43 AM
|
FIR-Final | 6/28/2004 | 6/29/2004 | 6/29/2004 | A | FAIL |
Rick Jackson
|
|
|
marva; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need manual pull fire alarm at exit by kitchen; if local alarm then manual pulls need signs - Local alarm - call 911; need zone breakdown of fire alarm zones 6/29/2004 9:58:41 AM
|