BLD-Final | 5/8/2006 | 5/9/2006 | 5/9/2006 | P | PASS |
Tony Young
|
|
|
nancy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIR-Final | 5/8/2006 | 5/9/2006 | 5/9/2006 | A | PASS |
Troy Cobbley
|
|
|
Life safety finaled. Structural inspector approved the use of the second exit out the front of the store for the secondary exit. This door has a crash bar and exit sign/emergency light.
|
Permanent Occupancy | | 5/9/2006 | 5/9/2006 | | DONE |
|
|
|
|
BLD-Final | 4/5/2006 | 4/6/2006 | 4/7/2006 | A | FAIL |
Tony Young
|
|
|
nancy zurcher- ###-#### call 1st before insp temp. signed need f/l/s 1st
|
BLD-Final | 4/4/2006 | 4/4/2006 | 4/6/2006 | P | CANC |
Tony Young
|
|
|
nancy zurcher- ###-#### call 1st ; Phone #: ###-#### rescheduled
|
MIS-Aging Inspection | 4/4/2006 | 4/4/2006 | 4/4/2006 | | PASS |
Tony Young
|
|
|
|
BLD-Final | 2/2/2006 | 2/2/2006 | 2/2/2006 | P | PART |
Tony Young
|
|
|
nancy zurcher- ###-#### call 1st before insp temp. signed
|
FIR-Final | 2/2/2006 | 2/2/2006 | 2/2/2006 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was issued. Per Sam Rogers, Ron Hill and I the owner is to utilize the front exit that was shown to be blocked as a temporary second exit until the rear exit has been revised to meet plans. Provide two 2A10BC fire extinguishers mounted no higher than 48" AFF with current inspection tags. Mount in locations as discussed. Repair the exit sign at the front exit. Cover all electrical outlets. Remove bar/dead bolt from the rear exit door and provide approved hardware. Both doors must open with a single motion. Both doors must swing out. Provide exit sign/emergency light at the rear door.
|