BLD-Final | 4/26/2006 | 4/27/2006 | 4/27/2006 | P | PASS |
Jim Sly
|
|
|
###-#### Duane OK for Perm Occ... No Occ Req card on site..... :(
|
FIR-Final | 4/26/2006 | 4/27/2006 | 4/27/2006 | P | PASS |
Forrest France
|
|
|
The required corrections have been verified for completion, life safety is acceptable, no signature card available on site at this time, contact to provide at next inspection.
|
Permanent Occupancy | | 4/27/2006 | 4/27/2006 | | DONE |
|
|
|
|
BLD-Final | 2/27/2006 | 3/2/2006 | 3/2/2006 | A | FAIL |
Jim Storey
|
|
|
duane marler- ###-#### -call 1st before insp -pending fire fn
|
FIR-Final | 2/27/2006 | 3/2/2006 | 3/2/2006 | A | FAIL |
Forrest France
|
|
|
Remove manual thumbturns at the main entry/exit door and the door from warehouse area, keyed locking hardware is allowed at the main entry/exit with signage above the door, cover open electrical boxes and secure loose/unused wire, provide fire extinguishers as discussed for the office and warehouse areas, provide building address.
|