Permanent Occupancy | | 2/9/2007 | 2/9/2007 | | DONE |
|
|
|
|
FIR-Final | 1/31/2007 | 1/31/2007 | 1/31/2007 | P | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
BLD-Final | 9/1/2006 | 9/5/2006 | 9/5/2006 | P | PART |
Mike Jordan
|
|
|
julie-- ###-####--pending fire fn. Temp occ given. All bldg. nonconformances listed on life safety c/n. Will be ok for perm occ once life/safety has finaled.
|
FIR-Final | 9/1/2006 | 9/5/2006 | 9/5/2006 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given until the fire extinguisher is provided with a current inspection tag, the exit signs and emergency lights are repaired, remove the dead bolts from the rear exit, provide automatic flush bolts for the inactive leaf of the main exit and provide sprinkler coverage at the rear door. The manual bolt at the rear exit could remain, exception for storage areas, as long as the exit signs are removed since only one exit is required which is at the front of the tenant.
|