MIS-Aging Inspection | 8/22/2011 | 8/22/2011 | 8/29/2011 | | DONE |
Tony Young
|
|
|
|
DOC - Permit Finaled | 8/29/2011 | 8/29/2011 | 8/29/2011 | P | PASS |
Tony Young
|
|
|
done
|
PLM-Final | 5/23/2011 | 5/23/2011 | 5/23/2011 | A | PASS |
Daryl Spivey
|
|
|
vacuum breakers installed ok on eye wash..........ds
|
MIS-Aging Inspection | 4/21/2011 | 5/21/2011 | 5/23/2011 | P | PASS |
Daryl Spivey
|
|
|
vacuum breakers are installed...........ds
|
MIS-Aging Inspection | 4/18/2011 | 4/18/2011 | 4/22/2011 | | PEND |
Tony Young
|
|
|
|
MIS-Aging Inspection | 2/16/2011 | 2/16/2011 | 2/22/2011 | | PEND |
Tony Young
|
|
|
|
MIS-Aging Inspection | 12/15/2010 | 12/15/2010 | 12/17/2010 | | PEND |
Tony Young
|
|
|
|
MIS-Aging Inspection | 9/17/2010 | 9/17/2010 | 9/23/2010 | | PEND |
Tony Young
|
|
|
|
MIS-Aging Inspection | 7/8/2010 | 7/8/2010 | 7/13/2010 | | PEND |
Tony Young
|
|
|
|
PLM-Conference | 3/9/2010 | 3/10/2010 | 3/10/2010 | P | PASS |
Daryl Spivey
|
|
|
Mike Levett ###-#### Met with Mike and looked at eyewash stations. at this time they have an inline check valve. This is not an approved backflow device. A PVB needs to be installed at both locations. I called DeBest, Jim McCall, and notified him that they installed the eyewashes incorrectly and the need to install PVB's at both locations.................ds
|
PLM-Conference | 3/8/2010 | 3/9/2010 | 3/9/2010 | A | CANC |
Daryl Spivey
|
|
|
Call Lee Rice for details AND call Mike Levet for access ###-#### rescheduled.........ds
|