MIS-Aging Inspection | 9/25/2014 | 9/25/2014 | 10/3/2014 | | PASS |
Dave Hannah
|
|
|
|
DOC - Permit Finaled | 10/3/2014 | 10/3/2014 | 10/3/2014 | P | PASS |
Dave Hannah
|
|
|
|
MIS-Aging Inspection | 6/26/2014 | 6/26/2014 | 6/30/2014 | | PASS |
Dave Hannah
|
|
|
|
MEC-Final | 3/27/2014 | 3/27/2014 | 3/27/2014 | A | PASS |
Bill VanDegrift
|
|
|
Per Bill Vandegrift - passed 3/25/14. Plumbing pass in attached PLM permit from JMD
|
PLM-Conference | 3/5/2014 | 3/5/2014 | 3/5/2014 | P | PART |
Bill VanDegrift
|
|
|
for salon temp occupany // Larry Phone #: ###-#### 1) air gap required at the T&P line termination 2) provide vacuum breaker at the hair wash sink 3) provide a fresh air hood upstream of the filter rack at the RTU 4) when the tenant relocates from this tempory location the two sinks will be removed and the waste line will be capped at the riser 5) all work to be permitted
|
MEC-Conference | 3/5/2014 | 3/5/2014 | 3/5/2014 | P | FAIL |
Troy James
|
|
|
for salon temp occupany // Larry Phone #: ###-#### Need to provide fresh air to the return duct at rtu. Fresh air intake to be installed upstream of filter.
|