MIS-Aging Inspection | 7/17/2017 | 7/17/2017 | 7/17/2017 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 7/17/2017 | 7/17/2017 | 7/17/2017 | P | PASS |
Mike Jordan
|
|
|
A building permit was issued in 2010.
|
ELE-Conference | 1/25/2016 | 2/1/2016 | 2/1/2016 | A | DONE |
Rock A. Hudson
|
|
|
Check permit status ELE15-00284 pulled for shop
|
ELE-Final | 2/1/2016 | 2/1/2016 | 2/1/2016 | A | PASS |
Rock A. Hudson
|
|
|
Check permit status ELE15-00284 pulled to cover shop
|
BLD-Final | 1/25/2016 | 1/25/2016 | 1/25/2016 | P | CANC |
Rock A. Hudson
|
|
|
as per Rock See ELE notes
|
ELE-Conference | 1/25/2016 | 1/25/2016 | 1/25/2016 | P | FAIL |
Rock A. Hudson
|
|
|
as per Rock Shop wired with out permits. 400.8- Flexible cords shall not be used as substitute for fixed wiring. 400.8- Flexible cord shall not be installed in walls, or ran through floors, or ceilings. 210.8- All 120 volt 15 and 20 amp receptacle outlets shall have GFCI protection. Date on 12-2 NM cable 10-10-2012. 7 days to secure permit for shop electrical and call for preliminary conference to discuss.
|