MIS-Aging Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 11/2/2016 | 11/2/2016 | 11/2/2016 | P | PASS |
Mike Jordan
|
|
|
Electrical has passed final inspection.
|
ELE-Final | 5/2/2016 | 5/10/2016 | 5/10/2016 | A | PASS |
James Ady
|
|
|
Check cords from ceiling in packing area. Check in at security desk Strain relief installed and outlets labeled Final ok
|
ELE-Final | 4/18/2016 | 5/2/2016 | 5/2/2016 | A | CANC |
Rock A. Hudson
|
|
|
Check for removal of extension cords in packing area. Check in at security desk. Rescheduled
|
ELE-Conference | 4/18/2016 | 4/18/2016 | 4/18/2016 | P | FAIL |
Rock A. Hudson
|
|
|
400.8(1)- Flexible cords shall not be used as substitute for fixed wiring of structure. Extensiion cords connecting to ceiling boxes down to equipment in packing area shall be removed. Extension cords not used as per listing. If additional power needed in packing area hard wired receptacles shall be istalled. Please call number listed on correction notice to schedule a time to meet to confirm removal.
|
ELE-Conference | 3/15/2016 | 3/18/2016 | 3/18/2016 | P | DONE |
Rock A. Hudson
|
|
|
Ray (fire) ###-#### No return phone calls from contacts. Unable to locate illegal work.
|
ELE-Final | 3/18/2016 | 3/18/2016 | 3/18/2016 | P | PASS |
Rock A. Hudson
|
|
|
Ray (fire) ###-#### Final ok
|
ELE-Conference | 3/11/2016 | 3/14/2016 | 3/15/2016 | A | CANC |
Rock A. Hudson
|
|
|
Roy (Fire) Phone #: ###-#### Called no return call unable to locate area in question. Rescheduled for Friday.
|