Permit NumberMIS17-00009
StatusFinaled
Name IDAHO TRANSPORTATION DEPARTMENT GE
Site Address 3311 W STATE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
misc ele work done incorrect
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
MIS-Aging Inspection4/13/20174/13/20174/14/2017 DONE
DetailsTony Young
DOC - Permit Finaled4/14/20174/14/20174/14/2017PPASS
DetailsTony Young
FIR-Conference1/12/20171/12/20171/12/2017PFAIL
DetailsMark Moncarr
some work was done incorrectly. Talked to Aaron at Idaho Transportation Dept. Priority Electric had replaced an 80a 3-pole breaker for an A/C unit on the rooftop. They removed the old breaker that had burnt up. Panels bussing is melted where existing breaker was located. New breaker was installed a few spots above that location. The new breaker was installed incorrectly which in turn made the contractor cut a portion of panel to fit the new breaker. Either the bussing needs to be replaced, or a whole new panel needs installed. Left correction notice with Aaron. All corrections need to be completed correctly. NEC 110.3