MEC-Final | 9/26/2017 | 9/26/2017 | 9/26/2017 | P | PASS |
Chad Schwendiman
|
|
|
1:30
|
DOC - Permit Finaled | 9/26/2017 | 9/26/2017 | 9/26/2017 | P | PASS |
Chad Schwendiman
|
|
|
1:30
|
MEC-Final | 9/20/2017 | 9/20/2017 | 9/20/2017 | A | PART |
Chad Schwendiman
|
|
|
Alberto ###-#### - temporary occupancy okay. Need to use approved gas flex on commercial cooking appliances
|
PLM-Final | 9/5/2017 | 9/5/2017 | 9/5/2017 | P | PASS |
Dan Ediger
|
|
|
Call for access- Ablerto Phone #: ###-####
|
PLM-Final | 8/31/2017 | 8/31/2017 | 8/31/2017 | P | NH |
Dan Ediger
|
|
|
Alberto-to get C of O Phone #: ###-####
|
PLM-Conference | 8/1/2017 | 8/1/2017 | 8/1/2017 | P | PEND |
Dan Ediger
|
|
|
C of O- Alberto Phone #: ###-####. 1. Have the double check valve premise protection certified. 2. Replace the expansion tank. 3. Remove the valve from the mop sink faucet spout. 4. Perm. cap all unused plumbing. 5. Raise the vacuum breaker on the three compartment sink faucet 12" and support. 6. Support the drain on the three comp. sink. Tenant states no drink machines used. Bakery.
|
MEC-Conference | 8/1/2017 | 8/1/2017 | 8/1/2017 | P | FAIL |
Chad Schwendiman
|
|
|
For C of O- Alberto Phone #: ###-#### - All equipment needs to be listed and labeled, need all equipment being installed under the class 1 hood installed to be able to check clearnces. Need to support gas piping under hood.
|