DOC - Permit Finaled | 5/16/2018 | 5/16/2018 | 5/16/2018 | P | PASS |
Jim Sly
|
|
|
At the time of the final inspection on 5/11/18, no access was provided by the contractor. A visual inspection was conducted around the perimeter of the structure. To the best of my knowledge, minimum code provisions were met.
|
MEC-Conference | 2/5/2018 | 2/6/2018 | 2/6/2018 | A | PART |
Bill VanDegrift
|
|
|
conference request from general contractor, house fire from gas fire place. met general contractor, DeWaine Kuehl, fire prevention officer, Brian Scoles PDS, HVAC contractor and Joe Bertwell fire place manager from D&B. termination didn't appear to have been sealed and attachet to flue, clearances at flue not met, fire blocking missing. see attached pictures. there are three homes 6121, 6123 and 6125, done by the same contractor, fire was at 6125. contractor will contact us when the other two fireplaces are exposed to check out the clearances and installation methods. Thee are no notes in the inspection pertaining to the fire place rough ins.
|
MEC-Conference | 2/5/2018 | 2/6/2018 | 2/6/2018 | A | DONE |
Brian Scoles
|
|
|
See Bill V notes
|