Permit NumberMIS19-00057
StatusFinaled
Name CORY LANE LLC
Site Address 9327 W CORY LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Caller reporting maintenance man doing electrical work that is not up to code. Specifically, check the fire suppression box in the kitchen in the main dining room.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
MIS-Aging Inspection1/14/20201/14/20201/15/2020 DONE
DetailsTell Riley
DOC - Permit Finaled1/15/20201/15/20201/15/2020PPASS
DetailsTell Riley
ELE-Final 3/11/2019 3/11/2019 3/11/2019 A PASS
DetailsTom Saunders
permit was pulled ELE19-00805
inspected and resulted 3/7/19
MIS-Aging Inspection3/1/20193/8/20193/11/2019APASS
DetailsTom Saunders
permit pulled ele19-00805
ELE-Final3/11/20193/11/20193/11/2019APASS
DetailsTom Saunders
permit was pulled ELE19-00805
inspected and resulted 3/7/19
ELE-Final3/7/20193/7/20193/7/2019PPASS
DetailsDaryl DeGrange
Job permited by ELE19-00805 completed final, final ok
FIR-Conference3/1/20193/1/20193/1/2019PCANC
DetailsTroy Cobbley
Per the electrical inspector the will be no requirement for any inspection by myself.

Permits Phone #: ###-####
ELE-Conference3/1/20193/1/20193/1/2019PFAIL
DetailsTom Saunders
Permits Phone #: ###-####...
1) wiring done without permit-circuits added in kitchen
2) added outlets need GFI protection
3) outlet shows short and not being protected by breaker
4) licensed electrical contractor shall pull permit
and make corrections within 5 days