MIS-Aging Inspection | 7/24/2020 | 7/24/2020 | 7/30/2020 | | DONE |
Jim Storey
|
|
|
4005 W CASSIA ST 2020-01-17T00:00:00-07:00 2020-01-17T13:53:24.633-07:00 ELE-Final P PASS 327
|
DOC - Permit Finaled | 7/30/2020 | 7/30/2020 | 7/30/2020 | P | PASS |
Jim Storey
|
|
|
4005 W CASSIA ST 2020-01-17T00:00:00-07:00 2020-01-17T13:53:24.633-07:00 ELE-Final P PASS 327
|
MIS-Aging Inspection | 4/23/2020 | 4/23/2020 | 4/23/2020 | | DEFR |
Jim Storey
|
|
|
|
ELE-Final | 1/17/2020 | 1/17/2020 | 1/17/2020 | P | PASS |
Rock A. Hudson
|
|
|
Able to confirm correction has been done by solar contractor. Final ok
|
MIS-Aging Inspection | 1/14/2020 | 1/14/2020 | 1/16/2020 | | FAIL |
Rock A. Hudson
|
|
|
Drove by and left correction notice explaining issue that needs attention and to call so I could explain further. Waiting for reply. After hours on 1/15/2020 Fred Jones 949- 0989 called and left message. I returned call at 8:15am 1/16/2020 received no answer and was unable to leave message due to voice mail box had not been set up yet.
|
ELE-Conference | 3/4/2019 | 3/4/2019 | 3/4/2019 | P | FAIL |
Rock A. Hudson
|
|
|
ele work w/o permits Existing circuit to AC at rear of dwelling. BCC 4-05-32 No code violationg to be retained. 110.11- Materials installed outdoors shall be rated for outdoors. 110.12- Materials shall not be damaged. NM cable runs exposed on back of dwelling to AC unit has sun exposure damage. 334.12- NM cable shall not be installed in a wet location, shall not be installed in direct sunlight.
25 day notice to have corrected. Dircuit to AC unit shows damage from exposure. Replace with an approved wiring method
|