Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMIS19-00225
StatusIssued
Name JRS PROPERTIES III L P
Site Address 415 S 9TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
as per Mike Jordan-work left undone and HAVC work done w/o permits
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Final10/17/201910/17/201910/17/2019PPART
DetailsRock A. Hudson
Work completed under ELE19-01088. ELE Final ok
BLD-Conference7/30/20197/30/20197/30/2019PCANC
DetailsMike Jordan
MEC-Conference7/30/20197/30/20197/30/2019PFAIL
DetailsChad Schwendiman
per Mike J-mec work done w/o permit - TVR installed a new A/C without a permit. I called them and they are going to get one pulled
ELE-Conference7/30/20197/30/20197/30/2019PFAIL
DetailsRock A. Hudson
ELE and MEC- Newer AC unit on Northwest corner, no permit found for ELE or MEC.
Misc electrical issue left when last tenant vacated.
All Items found in other areas not in scope of work covered by BLD18-03533.
BCC 4-05-32- Code violations not to be retained.
Unable to locate mechanical permit for newer AC unit located on northwest corner.
110.3- Double duplex receptacle located in conference room not working. Found wire damaged by others, left damaged in ceiling.
110.12(B)- Repair all open and unsecured conduits.
210.63- A 15 or 20 amp 120 volt receptacle outlet shall be installed with in 25' of newer AC unit.
314.23- Boxes shall be secured to structure. Receptacles and MC hanging laying on top of file cabinet.
408.4- Panel directory for panel 2 shall be complete.
440.14- A disconnecting means shall be provided for newer AC unit located on N.W. corner.