Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberMIS19-00391
StatusIssued
Name NUKIC SEAD
Site Address 2480 N MAPLE GROVE RD
Project Namepermit
Customer Number 
ePlanReviewNo
Description
work being done without electrical permit for correct wiring
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Conference11/19/201911/19/201911/19/2019PFAIL
DetailsRock A. Hudson
BCC 4-0517- Unlawful electrical procedures-
(1)- It shall be unlawfull to alter any electrical wiring or equipment without first securing an electrical permit.
BCC 4-05-32- Code violations not to be retained.
334.12(B)(4)- NM cable shall not be installed in wet or damp locations. NM cable exposed on exterior of house with short sections of PVC conduits installed over it. Also under back patio and jump to outdoor sheds. Expose is a wet location, interior of a conduit is a damp location.