MEC-Conference | 5/28/2020 | 5/28/2020 | 5/28/2020 | A | DONE |
Chad Schwendiman
|
|
|
Met onsite with Intermountain Gas to go through and evaluate the service space on the gas meters. Buildings A, B, C, D and E all need the A/C unit in front of the gas meter moved to a different location. We marked one unit on the back side of building G that needs to be slide forward away from the meters. It looks like this can be done without disconnecting the A/C. Buildings F, H, I, and J are all okay and no units need to be moved. According to Intermountain Gas, the A/C unit in front of the meter for C103 needs to be moved within the next two weeks for them to complete their required change out of the meter. The rest of the units need to be moved within 90 days.
|
MEC-Conference | 5/21/2020 | 5/21/2020 | 5/21/2020 | P | FAIL |
Chad Schwendiman
|
|
|
ac install in front of gas meters making them inaccessible per Chad S.- Issued a correction notice stating they need to maintain 30" wide and 30" deep working space in front of all gas meters. Per 306.1 of the 2012 IFGC.
|