Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberNAF14-00006
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 3600 PROSPECT WAY
Project NameDUPLEX
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a three level duplex. Each half of the duplex is a separate fire protection system. The duplex is protected using NFPA 13D. The piping is CPVC with extended coverage residential sprinklers.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final3/4/20153/5/20153/5/2015APASS
DetailsTroy Cobbley
Permit finaled. The surface mounted lights in the garage have been rotated out of the way.
INSP-Final3/3/20153/4/20153/4/2015PFAIL
DetailsTroy Cobbley
All items appear ok except the four pendant heads in the garage are blocked by surface mounted lights.
INSP-Final1/16/20151/20/20151/20/2015APART
DetailsTroy Cobbley
Only Lot 10 (3606) is passed. Lot 9 is not complete.
INSP-Final1/11/20151/12/20151/12/2015ACANC
DetailsTroy Cobbley
Cancel per Anthony due to notification issues.
INSP-Sprinkler Rough-in11/17/201411/17/201411/17/2014PPASS
DetailsTroy Cobbley
As-built/revised installation verified. Tenting verified. Piping can be covered.
INSP-Sprinkler Rough-in/Hydro11/3/201411/4/201411/4/2014PPART
DetailsTroy Cobbley
The hydro test passed for both overhead systems. Heads have been added in the fire places and the missing head provided in the lower level south room. As per previous correction comment as-builts need to be provided. Piping can not be covered until the as-builts are addressed and tenting inspection has been performed.
INSP-Sprinkler Rough-in/Hydro10/30/201410/31/201410/31/2014PFAIL
DetailsCraig D. Hanson
heads need to installed in fireplace chase's. head needs installed in new room 1st floor S unit. As builts need to be submitted. Re-hydro after instilation of heads.