Permit Information
Permit NumberNAF14-00010
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 3590 N PROSPECT WAY
Project NameDUPLEX
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a three level duplex. Each half of the duplex is a separate fire protection system. The duplex is protected using NFPA 13D. The piping is CPVC with extended coverage residential sprinklers.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final7/13/20167/15/20167/15/2016APASS
DetailsKatie Marron
Unit 3594 final test completed satisfactory. Scope of work complete. Permit Finaled.
INSP-Final6/23/20166/28/20166/28/2016APART
DetailsKatie Marron
Walk through completed. Flow switch was not wired so acceptance test was not completed. To be rescheduled once switch is wired.
INSP-Conference6/7/20166/7/20166/7/2016PDONE
DetailsKatie Marron
Called Anthony with Thorpe for a status update. The primary contractor is close to having all finishes done and then the final will be called in. System test has been previously completed.
INSP-Final3/28/20163/29/20163/29/2016PPART
DetailsKatie Marron
Unit 3590 Scope of work complete. Flow test completed satisfactory.

Unit 3594 still needs final test.
INSP-Final3/28/20163/28/20163/28/2016PCANC
DetailsTroy Cobbley
Please call Anthony when you are headed out! Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in1/26/20161/26/20161/26/2016PDONE
DetailsKatie Marron
Reinspected @ 4pm. Adjustments/additional insulation added. At time of inspection tenting ok.

Tenting inspection @ 1:30pm. Found a trouble spot in small bathroom. Called Anthony to adjust insulation.
INSP-Sprinkler Rough-in1/20/20161/21/20161/21/2016ANR
DetailsKatie Marron
Tenting was not complete at time of inspection (10:30 am). Was not able to reinspect, inspection needs to be rescheduled.
INSP-Sprinkler Rough-in/Hydro1/14/20161/15/20161/15/2016APASS
DetailsKatie Marron
Unit 3590 - Tenting inspection Ok and revised approved plans on site. Roughin complete, Ok to cover all.

Unit 3594 needs tenting inspection.
INSP-Sprinkler Rough-in/Hydro1/8/20161/8/20161/8/2016PPART
DetailsKatie Marron
Rough-in inpection pass for #3594 and pending resubmittal approval for #3590.

Hydro static test completed satisfactory for both.

Still to be completed: backflow preventer and main valve. No tenting completed to date.