Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberNAF15-00014
StatusFinaled
Name JASON MINNICK
Site Address 215 E 41ST ST
Project NameTRAILWINDS APARTMENTS
Customer Number 
ePlanReviewNo
Description
Installation of sprinkler monitoring, elevator recall with shunt, hallway smoke and CO detection, dwelling smoke and CO detection, corridor notification and low frequency horns in sleeping rooms.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final11/3/201511/4/201511/4/2015PPASS
DetailsKatie Marron
Scope of work complete. Permit Finaled. Sprinkler Flows and FSDs tested ok.
INSP-Final11/2/201511/3/201511/4/2015ACANC
DetailsKatie Marron
Cancelled per phone call with contractor.
INSP-Alarm Testing10/29/201510/30/201510/30/2015APART
DetailsThomas Walsh
Conducted test of fire alarm system for the south wing - north wing already tested for TCO of that wing.
Tested unit SDs and CO dtectors, common area SDs in corridors, elevator recall functions, etc. All tested OK.
NOTE: Fire sprinkler contractor was not available to conduct flow tests for the fire sprinkler systems. Also did not have enough time to test FSDs. These will have to be tested at next inspection.
INSP-Alarm Testing10/29/201510/29/201510/29/2015PDONE
DetailsTroy Cobbley
No actual testing was performed. I did a walk through of the remaining building which included the 1st, 2nd and 3rd floors. I marked on the city approved plans locations of deficiencies which included overspaced smoke detectors in all of the main corridors, one strobe in a corridor that needs to be relocated due to an obstruction and multiple smoke detectors in the apartments that are located less than 3'-0" from bathrooms with tubes/showers. I also verified with Jim Page that as per Katie's previous entry the 2nd and 3rd floor recall still needs to be performed as well as the actual flowing of water for the flow switch testing.
INSP-Alarm Testing10/1/201510/1/201510/1/2015PPASS
DetailsKatie Marron
Fire alarm system tested besides devices on south west side. Flow switches tested manually (no flow). Partial final. Elevator 2nd and 3rd floor recall still to be conducted.
INSP-Alarm Testing9/30/20159/30/20159/30/2015PFAIL
DetailsKatie Marron
Verified all devices are correct. Tested four detectors, three worked. Room numbers reported do not match actual marked room numbers. Elevator recall from 1st floor worked. Contractor to fix programing for correct room number identification.