Permit Information
Permit NumberNAF15-00045
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5601 CHINDEN BLVD
Project NamePRIMARY HEALTH
Customer Number 
ePlanReviewNo
Description
[Primary Health]
The fire sprinkler scope of work consists of protecting a single level office/medical building. A new 6”x72’± C-900 underground service will supply a new 4” backflow preventer. The 4” cross main will supply 1 ½” branch lines. There is above and below protection.

(PRIMARY HEALTH) Permit for the construction of a new 5,618 sq. ft. health care building with exam and procedure rooms, offices and accessible restrooms per the approved plans and the attached engineering. This building is fully fire sprinklered.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final5/24/20165/25/20165/25/2016PPASS
DetailsTroy Cobbley
Permit finaled. Forward flush passed.
INSP-Final5/20/20165/23/20165/23/2016ACANC
DetailsTroy Cobbley
Tyler is the contact. Thanks. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro5/4/20165/4/20165/4/2016PPASS
DetailsTroy Cobbley
Overhead Hydro passed
INSP-Sprinkler Rough-in/Hydro5/2/20165/3/20165/3/2016AFAIL
DetailsKatie Marron
Hydrostatic test Fail. Will need to be recompleted.

Roughin completed satisfactory. Ok to cover.
Verified upright sprinklers in concealed pocket spaces, 4 dry sidewalls, earthquake bracing and pipe sizes match resubmitted plans as noted from previous inspection. Additionally inspected pendant drops.

Minor items to be completed for Final:
-Missing coverage at File room (pendant to be moved over)
-revised set of plans onsite
- remove tape from uprights in janitor rm and ensure they have not been painted
INSP-Supply line flush4/26/20164/27/20164/27/2016ADONE
DetailsKatie Marron
Underground flush
INSP-Supply line flush4/25/20164/26/20164/26/2016PCANC
DetailsKatie Marron
Should be under permit NAF15-00044. Rescheduled due to buried supply valve.
INSP-Sprinkler Rough-in/Hydro4/25/20164/26/20164/26/2016PCANC
DetailsKatie Marron
Wrong permit number. Underground is NAF15-00044. Inspection input under that.
INSP-Final2/23/20162/24/20162/24/2016AFAIL
DetailsTroy Cobbley
Project is not ready for final as requested. Project is not ready for rough-in yet. Missing earthquake bracing, missing upright coverage in pockets at the main entry, pipe sizing of riser nipples and starter pieces do not match the approved plans, missing dry sidewall heads in the exterior pockets. I gave the general contractor the ok to cover hard lids as indicated on the plans. Resubmittals are required showing all changes such as piping size changes and the additional fittings used, and additional sprinkler heads.