Permit Information
Permit NumberNAF16-00012
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 515 E 50TH ST Unit: BLDG A
Project NameLEGACY APARTMENTS BLDG A
Customer Number 
ePlanReviewNo
Description
[Legacy Apartments Building A]
The fire sprinkler scope of work consists of 3 level apartment building protected by a NFPA 13R wet system. There is a small amount of heat tracing where the main crosses the open corridor.

See NAF15-00038 for the underground permit
See NAF15-00026 for building fire code plan review.

Legacy Apartment building "A". Permit for a new 3 story 24,116 sqft apartment building consisting of 24 units. Each dwelling unit shall contain an emergency guide in accordance with IFC section 408.9 indicating evacuation routes, smoke alarms and building fire extinguisher locations. This building is required to be fire sprinklered with an approved fire alarm system in accordance with NFPA 13 and NFPA 72. Separate fire protection permits will be required; as regulated by North Ada County Fire & Rescue District
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final4/17/20174/18/20174/18/2017PPASS
DetailsJim Page
Previously noted items have been repaired, sprinkler heads next to registers on level 3 will be changed to an intermediate temperature head (sprinkler heads are less than 24 inches away from heat register). Final fire sprinkler passed/complete
INSP-Final4/13/20174/14/20174/14/2017PFAIL
DetailsScott Arellano
Hallway Sprinkler heads obstructed by ceiling light fixture at multiple units. Sprinkler heads need to be relocated to 36 inches from fixture or fixtures need to be replaced with recessed lighting.
INSP-Sprinkler Rough-in12/14/201612/14/201612/14/2016PDONE
DetailsKatie Marron
At time of inspection tenting completed satisfactory. One uncovered spot identified, insulators on site to correct.
INSP-Sprinkler Rough-in/Hydro12/12/201612/13/201612/13/2016APASS
DetailsKatie Marron
All three system satisfactorily hydro tested. Roughin third floor completed. Heat tape has been installed.

-Tenting was not complete and will need to be reinspected. No dry sidewalls installed yet
INSP-Sprinkler Rough-in11/29/201611/29/201611/29/2016PPART
DetailsKatie Marron
Rough-in completed satisfactory for 1st and 2nd floors.

Sidewalls and 3rd floor w/tenting still to be completed.