Permit Information
Permit NumberNAF16-00084
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 9995 W STATE ST
Project NameGRACE AT STATE ST ADDITION
Customer Number 
ePlanReviewNo
Description
[Grace at State Street Addition]
The fire sprinkler scope of work consists of connecting to an existing riser. Extending a new 6” bulk main to a new riser room. The main will supply one new wet system and one new dry system.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final6/29/20176/30/20176/30/2017ADONE
DetailsTroy Cobbley
Call prior to going Phone #: 9957215 >> Inspection requested via mobile web by Lonnie
DOC - Permit Finaled  6/30/2017 DONE
DetailsTroy Cobbley
as per Troy doc final-won't let him do it in the field
INSP-Final6/26/20176/27/20176/27/2017ACANC
DetailsTroy Cobbley
The fire alarm contractor is not ready for testing yet
INSP-Sprinkler Rough-in/Hydro5/17/20175/17/20175/17/2017PPASS
DetailsTroy Cobbley
Overhead hydro test for the dry system passed
INSP-Sprinkler Rough-in/Hydro5/15/20175/16/20175/16/2017APART
DetailsScott Arellano
Rough toc cover PASS. Crawl space and overhead inspected. Overbuild sprinklers to be heated with active heating through transfer grills from warehouse and lower office combined with insulation tenting. Finish sheet rock needs to be installed prior to final inspection.
INSP-Sprinkler Rough-in/Hydro4/28/20175/1/20175/1/2017APASS
DetailsJim Page
Tenting inspection complete, overhead fire sprinkler piping approved for cover.
INSP-Sprinkler Rough-in4/25/20174/25/20174/25/2017PPART
DetailsJim Page
Previously noted items for sway brace attachment corrected/completed, tenting/sway brace attachments approved for cover west of the fireplace, tenting still needs to be installed over the 6 inch supply main, main supply cannot be covered until tenting is inspected/passed.
INSP-Sprinkler Rough-in4/20/20174/20/20174/20/2017PPASS
DetailsTroy Cobbley
Did not make contact with Lonnie but met with the job superintendant Nacho. I gave approval for the piping in the Commons Area to be covered. Tenting in this area passed. I noted that the earth quake bracing needs to utilize through bolts at all connection points, not lag bolts. I discussed this with Nacho and he was going to let Lonnie know.
INSP-Sprinkler Rough-in/Hydro4/12/20174/13/20174/13/2017APASS
DetailsScott Arellano
2 hour hydro static test witnessed on wet system at West Wing.
INSP-Sprinkler Rough-in4/12/20174/12/20174/12/2017PPART
DetailsScott Arellano
Tenting Inspection on West wing wet system complete.



INSP-Sprinkler Rough-in/Hydro3/30/20173/30/20173/30/2017PPART
DetailsKatie Marron
Tenting for south wing. At time of inspection tenting ok. Verified missing baffles for dry system were installed.
INSP-Sprinkler Rough-in/Hydro3/29/20173/29/20173/29/2017PPART
DetailsKatie Marron
Rough-in completed on remaining wet and dry system.
*Straps missing on 4" wet in common space
*Verified missing drop corrected from previous inspection.
INSP-Sprinkler Rough-in3/16/20173/16/20173/16/2017APART
DetailsKatie Marron
Completed rough-in on wet and dry system for south wing up to common area (see site plans).
*One drop in hallway missing to be verified at tenting inspection.*
*Baffles required for dry system to be verified at tenting*
*Eaves are currently open to rest of ceiling space as indicated in plan review response for item 2*