INSP-Final | 10/3/2017 | 10/3/2017 | 10/3/2017 | P | PASS |
Troy Cobbley
|
|
|
Call prior to going Phone #: 4774515 >> Inspection requested via mobile web by Jeremiah Robinson
|
DOC - Permit Finaled | | | 10/3/2017 | | DONE |
|
|
|
finaled per Troy
|
INSP-Final | 10/2/2017 | 10/2/2017 | 10/2/2017 | P | FAIL |
Troy Cobbley
|
|
|
All items have been corrected except for the supply piping in the crawl space needs to comply with review note #3.
|
INSP-Final | 9/26/2017 | 9/27/2017 | 9/27/2017 | A | FAIL |
Troy Cobbley
|
|
|
Nothing attempted worked today except the domestic water did shut down upon activation of the flow switch.. To be rescheduled
|
INSP-Final | 9/25/2017 | 9/25/2017 | 9/25/2017 | P | CANC |
Troy Cobbley
|
|
|
Not ready yet per electrician. Need the smoke alarms connected to the flow switch per review note #2.
Call for access Phone #: 2085504599 >> Inspection requested via mobile web by Stevie Ray
|
INSP-Final | 9/6/2017 | 9/7/2017 | 9/7/2017 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2082974687 >> Inspection requested via mobile web by Josh Eaton
|
INSP-Sprinkler Rough-in/Hydro | 6/5/2017 | 6/6/2017 | 6/6/2017 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|