INSP-Final | 10/18/2017 | 10/18/2017 | 10/18/2017 | P | DONE |
Troy Cobbley
|
|
|
life safety passed. the sprinkler system has been removed as per agreement
Call prior to going Phone #: 8018652758 >> Inspection requested via mobile web by Ben johnson
|
DOC - Permit Finaled | | | 10/18/2017 | | DONE |
|
|
|
Per 430 Troy
|
INSP-Final | 8/24/2017 | 8/25/2017 | 8/25/2017 | A | PART |
Troy Cobbley
|
|
|
A partial final is being given with the fire dept's approval until the fire sprinkler system issue has been resolved as per the previous comments and emails
|
INSP-Final | 8/23/2017 | 8/24/2017 | 8/24/2017 | A | FAIL |
Troy Cobbley
|
|
|
Repair the emergency light in Kitchen and provide the missing exit sign and exit discharge light at the Ktichen exit door. Sprinkler modifications are still an issue.
|
INSP-Final | 8/22/2017 | 8/23/2017 | 8/23/2017 | A | FAIL |
Troy Cobbley
|
|
|
Provide exit discharge lights, provide missing exit signs and emergency lights, provide fire sprinkler modifications, mount fire extinguishers, mount address. Per conversation with scott arellano once all of the items except fire sprinklers are corrected a temporary occupancy can be allowed until sprinkler modifications are complete. Also per conversation with scott the fire sprinkler system will not require a sprinkler riser monitoring system. Per the site supervisor, Ben, State Fire is going to be the sprinkler contractor responcible for the modifications.
|